Skip to content

Technical glossary

VFD Terminals and Functions: GND, RDY, JOG Explained

What does GND RDY JOG mean on a VFD? A short glossary of common drive terminals and display messages, and how to confirm each one in your manual.

Direct answer

On a VFD, GND is the ground (earth) connection, RDY means the drive is ready to accept a run command, and JOG is a function that runs the motor at a low, fixed speed for short moves and tests. Exact behavior varies by model, so confirm each one in the manufacturer's manual.

Institutional content: Authomathika

Published:

Anyone who opens a drive cabinet or scrolls through a keypad will meet short labels such as GND, RDY and JOG. They look simple, but each one affects safety or how the motor starts. This glossary explains the most common meanings in generic terms. Labels, logic and defaults differ between models, so the manual of your specific drive always has the final word.

What does GND mean on a VFD?

GND is short for ground, the connection of the drive to the protective earth of the installation. On a power terminal it is usually marked PE or the earth symbol, and it ties the drive enclosure and the motor frame to the grounding system.

GND can also appear on control terminals, where it means something different: the reference (common) of the control circuit, used by analog inputs, digital inputs or a 24 V supply. This control common is not always the same as protective earth, and drives often have more than one common, for example one for analog signals and another for digital ones. Mixing them up can cause erratic readings or damage.

For the wiring side, see the guide on how to wire a VFD to a three-phase motor.

What does RDY mean and when does it appear?

RDY means ready: the drive is powered, has finished its self-checks, has no active fault and is able to accept a run command. On a keypad it is a status message or indicator light. On a terminal block it can be a relay or transistor output that signals the same condition to a PLC or panel light.

A drive that does not show RDY is usually waiting for something. Common reasons to check, without assuming any one of them:

SymptomProbable causeWhat to verify
RDY never appears after power-upActive fault or alarmFault log on the keypad
RDY appears, then disappearsSafety or enable input openedSafe torque off, enable and emergency stop circuits
RDY on, motor does not startRun command or reference missingControl source selection and reference source
RDY off after a tripFault latchedCause of the fault, then reset as the manual describes

Some manufacturers use other words for the same idea, such as Ready, Stop or Standby. The manual lists which one your model uses.

What is the JOG function?

JOG is a function that runs the motor at a low, fixed speed while a button or input is held, and stops it when released. It is used for short, controlled movements: checking the direction of rotation, positioning a machine, releasing a jam or testing a mechanism during commissioning.

Three points are worth knowing:

  1. JOG has its own speed setting, separate from the normal speed reference.
  2. It often uses its own acceleration and deceleration ramps.
  3. Depending on the model, JOG can be started from the keypad, from a digital input, or both, and it may only work when the drive is in a specific control mode.

Because JOG can move the machine without the normal start sequence, confirm that the area is clear and that the driven equipment can safely turn before using it. To understand how the speed itself is produced, read how a VFD controls motor speed.

What other terms appear on the display and terminals?

The list below covers common labels, described generically. Names differ by manufacturer.

  • FWD / REV: forward and reverse run commands or direction indicators.
  • STOP / RUN: state of the drive or the command that starts and stops it.
  • FLT / FAULT: an active fault that stops the drive until the cause is cleared.
  • ALM / WARN: an alarm or warning that does not necessarily stop the motor.
  • RST / RESET: input or key that clears a latched fault.
  • DI / DO: digital inputs and digital outputs.
  • AI / AO: analog inputs and analog outputs, commonly used for speed reference and feedback signals.
  • COM: common of a group of inputs or outputs.
  • L1, L2, L3 (or R, S, T): three-phase supply input.
  • U, V, W (or T1, T2, T3): output to the motor.
  • DC+, DC-, BR: DC bus and braking resistor connections, present on some models.
  • STO: safe torque off, a safety function that removes the ability to produce torque.

If you are new to the equipment, start with what a variable frequency drive is and what it is for, then see how to configure and program a VFD for parameters such as control source and reference.

Where do you confirm the meaning in the equipment manual?

Confirm every label in the manual of the exact drive model, in the current revision. The same abbreviation can mean different things in different families, and a firmware version can change a default.

A practical way to look it up:

  1. Read the nameplate on the drive and note the model, rating and firmware version if shown.
  2. Find the matching user or installation manual and open the terminal description chapter.
  3. Check the control terminal table for the function of each label, including which common it uses.
  4. Open the fault and alarm list for the meaning of status messages.
  5. Check the parameter list for the JOG speed, ramps and the source that enables it.
  6. If the project has a wiring diagram or panel documentation, compare it with the manual before assuming a label is used as printed.

For drives installed inside industrial panels and integrated with a PLC or supervisory system, the labels in the project drawings also matter. Authomathika works with electrical and automation scopes, so project documentation and drive wiring are part of the same review. You can see the areas on the Electrical and Automation pages.

Frequently asked questions

Is GND on a VFD the same as earth?
Not always. On power terminals GND usually means protective earth, while on control terminals it often means the common reference of the control circuit. Check the terminal table in the manual to see which one applies.
Why does my VFD not show RDY?
The drive is usually blocked by a fault, a missing enable or safety signal, or an incomplete startup. Read the fault log and the status of the enable and safety inputs, then follow the manual.
Is it safe to use JOG with the machine connected?
Only if the area is clear and the driven equipment can turn safely at low speed. Follow your plant procedures, and have a qualified person do the test.
Do all drives use the same labels?
No. Many labels are common, but names, logic and defaults differ by manufacturer, family and firmware. Always use the manual of your exact model.
Can I change the JOG speed?
Usually yes, through a dedicated parameter, but the parameter name and range depend on the model. Look for it in the parameter list of the manual.
VFD Terminals and Functions: GND, RDY, JOG Explained | Authomathika