Skip to content

Technical glossary

What Is an MCC? Motor Control Centers in Industry

Learn what a motor control center is, which components it contains, how it differs from a main switchboard and what data to send when specifying one.

Direct answer

An MCC, or motor control center, is the electrical assembly that groups the power supply, protection and control of the motors in one plant area. Each motor has its starter in a dedicated compartment, which organizes maintenance and integration with automation. Authomathika designs and builds custom MCCs.

Institutional content: Authomathika

Published:

An industrial plant runs dozens or hundreds of motors that drive pumps, conveyors, fans and agitators. Grouping the starters for those motors in a single assembly makes operation, maintenance and communication with the control system easier. That assembly is the MCC.

What is an MCC?

MCC stands for motor control center. It is an electrical assembly, usually low voltage, made of vertical sections and compartments that feed, protect and control the motors of one process area. Medium voltage MCCs also exist and are used for large motors.

The core idea is standardization. Each motor gets a starter unit built from the same types of components, labeled and separated from the others. The team can find a circuit quickly and work on one starter with less interference with the rest, depending on the construction form adopted.

Which components make up an MCC?

An MCC combines a distribution bus and the starter units. The most common components are:

  • Busbars: carry power from the incoming section to each vertical section and compartment.
  • Protective devices: circuit breakers or fuses that act on short circuits and overloads.
  • Switching devices: contactors that start and stop the motor.
  • Overload relays or intelligent relays: protect the motor and can report current, status and faults.
  • Electronic starters: soft starters and variable frequency drives, when the process needs a smooth start or speed control.
  • Control and indication: pushbuttons, pilot lights, terminals and the interface with the PLC or DCS.

What is the difference between an MCC and a main switchboard?

The difference is the function. The main low voltage switchboard receives power from the transformer and distributes it to the other panels in the installation. The MCC receives that power and delivers it to the motors, with individual protection and control.

CharacteristicMain switchboardMCC
Main functionDistribute power to other panelsFeed, protect and control motors
Position in the installationRight after the transformerAfter the switchboard, close to the process
Loads servedPanels, MCCs and distribution boardsMotors and process loads
Automation integrationMetering and breaker statusControl, status and diagnostics for each starter

In smaller installations both functions can share one assembly. To compare panel proposals, see how to choose an industrial electrical panel supplier.

What is an intelligent MCC?

An intelligent MCC is one where the starters communicate with the control system over an industrial network instead of exchanging only hardwired signals. Intelligent relays, soft starters and drives send the PLC or DCS data such as current, status, alarms and trip causes.

Operators can then see each motor on the SCADA screens, and maintenance can review fault history without opening the panel. The choice between a conventional and an intelligent MCC depends on the plant automation level, the network in use and what the team plans to do with the data.

Fixed or withdrawable MCC: how to choose?

In a fixed MCC, the components of each starter are mounted in the compartment and maintenance happens in place. In a withdrawable MCC, each starter sits in a drawer that can be removed and replaced with an equivalent one.

A withdrawable unit shortens motor downtime because the swap is fast. In return, the assembly takes more engineering and costs more. The fixed design usually suits processes where a short stop of one motor is acceptable. The decision should weigh how critical each load is and the spare parts strategy.

What data should you send to specify an MCC?

A clear specification avoids rework and lets you compare proposals on the same basis. Gather:

  1. Single line diagram and load list, with power, voltage and starter type for each motor.
  2. Supply voltage, frequency and short circuit level at the installation point.
  3. Environmental conditions such as dust, humidity, temperature and the required degree of protection.
  4. Construction form, fixed or withdrawable, and the space available in the electrical room.
  5. Communication network and signal list for automation.
  6. Spare capacity for expansion and requirements for documentation and testing.

Authomathika combines electrical engineering, manufacturing of custom electrical panels and automation. With the data above, the team can assess the scope and advise on the MCC configuration.

Frequently asked questions

What does MCC stand for?
MCC stands for motor control center. It is the assembly that groups the starters, protection and control of the motors in one plant area.
Can an MCC include variable frequency drives?
Yes. Starter units can use direct on line starting, a soft starter or a variable frequency drive, depending on what each motor needs. Heat dissipation and panel ventilation must account for this equipment.
Is an MCC always low voltage?
No. Most MCCs are low voltage, but medium voltage MCCs exist for large motors, with their own components and requirements.
What is the difference between an MCC and an automation panel?
The MCC handles power: it feeds and protects the motors. The automation panel houses the PLC, remote I/O and network devices that control the process. The two communicate through hardwired signals or an industrial network.

Send your scope and receive a technical assessment from the Authomathika team.