The Auth 300 is designed to work with 4 to 20 m signal, profbus PA or Hart. Designed primarily for Damper boilers and ovens operations. The Auth 300 actuates the arm of the Dampers positioning according to the output signal of the controllers, providing a perfect answer for the tuning of meshes.
- Compact and modular design;
- Easy installation;
- With integrated air filter;
- Easy setting of parameters;
- Time-tested and explosion-proof positioner;
- Feature change with facilities;
- Optional limit switch for pneumatic cylinder;
- Ideal for Dampers actuation of boilers and ovens;
- Robust for aggressive areas;
- Stem Protection for Aggressive Environments.
AUTH 300 Damper Actuator

TECHNICAL DATA |
Temperature limits: (operation) |
-40 to 85 ° C (-40 to 185 ° F) |
Storage |
-40 to 90 ° C (-40 to 194 ° F) |
Moisture Limits: |
0 to 100% RH |
Position feedback: |
Mechanical arm - With optional DPG from 4 to 20 ma |
Resolution: |
0.5% F.S |
Repeatability: |
0.5% F.S |
Hysteresis: |
1% F.S |
Positioner air consumption: |
5 bpm |
Air outlet capacity: |
13.6 Nm³ / h (8 SCFM) for 5.6 bar (80 psi) air supply |
Effect of the ambient temperature: |
0,8%/20 0C of span |
Pressure supply (compressed air): |
1.4 - 7 bar (20-100 psi) free of oil, dust, water and non-corrosive |
Recommended minimum filtration: |
40 μm |
Explosion test |
ExdmIIBT6 |
Cylinder specifications: |
Pneumatic Cylinder ISO |
- ISO 6431, VDMA 24562, NFE 49-003-1, BS and CETOP policies;
- Double action;
- Double damping;
- Anodized aluminum shirt;
- Injected aluminum head;
- Piston seals and polyurethane rod seals;
- Stainless steel rod with accordion protection and rod extension - maximum working pressure of the pneumatic cylinder 10 bar (the working pressure must meet the maximum of the positioner, ie 7 bar);
- Working temperature: -20 ° C to 85 ° C;
- With male support for articulation.
Mounting bracket: steel, with anchor for fixing to the floor.